AbleCool (RDHx)
High-Efficiency EC Fan Hybrid Thermal Platform
CDR42(EC)
38kW base capacity, scaling up to 50kW,
Powered by 4 EC centrifugal fans delivering 3900 CFM active airflow.
Utilizes AC 200–240V (1+1) redundant power supplies
Full-tier sensor array detecting temperature, differential pressure, condensation, and leakage.
Max 70 LPM fluid flow utilizing industry-standard FD83 Quick Dry Connectors.
| Model | CDR42(EC) |
| Support rack Form Factor | 42U - 52U |
| Dimension (Width) | 600 – 800 mm (23.62" - 31.50") |
| Dimension (Depth) | 337 mm (13.3“ ) |
| Cooling Capacity * | 38kW ( 50 kW /ATD=15C) |
| Fan Quantity | 4 pcs EC Centrifugal Fan |
| Active Air Flow** | 3900 CFM |
| Design Water Flow | Max: 70 LPM (18.5 GPM) |
| Water Fluid Quality | ASHRAE D-90564 |
| Max Power Consumption | 1.7KW |
| Power Supply | AC:200–240V(1+1) |
| Internal Sensor Detection | Temp. |
| Communication | SNMP, Modbus, Redfish API, BMC Link |
| Monitor control | Touch Panel、 Web UI |
| Operating Ambient Temperature | 15℃~45℃(59℉~113℉ |
| Operating Relative Humidity | 8~80%RH(No Condensing) |
| Operating Attitude | 0~3,048m(0~10,000ft) |
| Water Connection | Quick Dry Connector (FD83) |
| Shipping Weight (kg) | 252 |
| Dry weight(kg) | 114 |
| Wet Weight(kg) | 130 |
File Name
Update